    您當前的位置:首頁 > 技術文章 > Common faults and causes of zirconia oxygen analyzers

    Common faults and causes of zirconia oxygen analyzers

    發(fā)布時間: 2024-12-13  點擊次數(shù): 1056次

    1. System maintenance.

    If the oxygen indicator shows zero or no oxygen indication in the oxygen quantity converter, first check whether the oxygen indication circuit open. If the circuit is normal, check whether the zirconia probe is normal. At a temperature of 700℃, measure the DC millolt value of the oxygen cell. If the potential is greater than 1 millivolt and the resistance is greater than 100Ω, it indicates the probe is aged and needs to be replaced with a sensor or probe. If the potential is less than 1 millivolt and the resistance is less than100Ω, it indicates an open circuit in the wiring, which should be checked and handled one by one.

    2. constant temperature system failure.

    (1) If the heating temperature cannot be maintained, check whether there is a short circuit or open circuit in the resistance wire inside the heating furnace The normal resistance of the heating furnace wire is about 60-80Ω. If the resistance wire is open or the resistance measured by the multimeter less than 60Ω, the heating furnace wire should be replaced.

    (2) When the converter shows that the temperature is too high or out of control, it not only causes inaccurate oxygen display but also acceler the aging or damage of the zirconia head. At this point, you should immediately check if the thermocouple is open-circuited, or a multimeter to check the thermocouple. If the resistance is greater than 20Ω, it is judged that the thermocouple is open-cuited, and the thermocouple and zirconia head should be replaced; another reason for the temperature失控is: relay or temperature control circuit failure, relay or temperature control circuit failure will cause the oxygen converter to always be in one of the heating voltages of the heating furnace, thus leading to an increase in.

    3. oxygen cell fault.

    (1) After the oxygen cell has been used for a period of time, the contact points of its leads may become oxidized, resulting in contact or detachment. This can cause the Em value (in units of a multimeter) to fluctuate and become unstable. Observe the oxygen cell and take action.

    (2) When the oxygen signal deviation is too large or inaccurate, it may be due to a short circuit in the zirconia electrode, which case the wiring of the zirconia cell should be checked for short circuits. When the temperature does not rise, if the internal resistance is less than 0Ω, it indicates a short circuit in the electrode, and the zirconia head needs to be replaced.

    (3) During the operation of the oxygen measurement device, if the background potential exceeds 10mV or is less than -30mV, it must be recalibrated. If the background potential remains abnormal after calibration, it indicates that the probe has aged and can no longer be used.

    4. pneumatic circuit failure.

    (1) The zirconia head is clogged with ash, causing an obstruction in the reference gas circulation. This results in a decrease in probe output potential Em and an increase in the background potential Eo. In this case, blowing several times with a bulb syringe at the gas inlet of the will resolve the issue after the gas line is unclogged.

    (2) Oxygen cell ash blockage: The probe should be removed from the ash blockage and the filter should be reinstalled.

    (3) Probe leakage has a significant impact on the probe.

    5. The oxygen content on both sides of the boiler is too high.

    By adjusting the boiler combustion conditions, when starting or stopping the boiler fan or coal mill group, if the oxygen content deviation on both sides of the boiler is large, it is a normal phenomenon. Once the boiler combustion conditions stabilize, the oxygen content display will return to normal. If the unit adjustment is not in place and the deviation is large on both sides, it is necessary to check if the zirconia head is working properly by dismantling the transmitter for inspection. The device requires the operator to adjust the gas flow. The gaseous and reference state gases should continuously flow through the electrode without stopping, and there should be no dead ends. However, too large a flow will have a cooling effect, making the cell temperature uneven and causing errors. If the flow is too small, it is not only easy to form stagnant gas flow and dead zones but also may cause local changes in oxygen concentration due to the conduction of oxygen ions, thus affecting the accuracy of the measurement and causing deviations on both sides.

    6. On-site interference causes failures.

    For newly installed instruments, due to the strong electromagnetic field, when an unstable fault occurs, the first thing to consider is the interference issue.


產品中心 Products
在線客服 聯(lián)系方式 二維碼

服務熱線

0550-2409223

掃一掃,關注我們

皖公網(wǎng)安備 34118102000850號

国产一区二区三区av精品| 中文字幕奈奈美被公侵犯| 午夜福利不卡片在线播放| 大战丰满老熟妇重囗味视频| 国精品无码人妻一区二区三区| 99久久综合狠狠综合久久AⅤ| 人人妻人人爽人人做夜欢视频| 性一交一乱一美a片69xx| 鲁死你AV资源站| 欧美大尺寸suv欧美| 成人免费视频| 好硬啊进一得太深了a片| gogo全球专业高清摄影| xxxxxl日本17上线| 久久国产色av免费观看| 国产农村熟妇出轨videos| 47最大但人文艺术摄影| 国产精品美女久久久免费| 娇妻被领导粗又大又硬| 欧美综合色婷婷欧美综合五月| 两根撑到极致哭着求饶h| 女の乳搾りです在线观看| 巴西free性video极品| 国产国拍亚洲精品MV在线观看| 高中女厕原味卫生巾巾5565| 奶头被嘬的又大又硬h| 精品人妻无码一区二区三区蜜桃一| 精品欧洲av无码一区二区三区| 午夜福利一区二区三区在线观看| 精品人妻无码一区二区三区4| 欧洲aaaaa特级毛片| 粉嫩小又紧水又多a片| 在公交车上弄到高c了怎么办| 亚洲av无码乱码国产精品久久| 色情欧美片午夜国产特黄| 久久婷婷激情综合色综合俺也去| 大内密探之零零性性| 女人下边被添全过程a片小说| 欧美精产国品一二三产品区别| 国产亚洲欧美在线精品电影| 久久精品中文字幕一区二区三区|